My DATEC knows how to propose solutions for any equipment in the service industry, do not hesitate to consult us!
Thank you France Air for this mine of information:
Find below the air renewal rates to be implemented for each type of commercial building.
Offices
Type of room
Flow rate (m3/h)
Labour code per person.
RSDT
per person.
per room
Offices
Air inlet
Hall receiving the public
25
18
–
Air inlet
Reception and information desk
30
25
–
Air inlet
Waiting room
25
18
–
Air inlet
Individual and collective offices
25
18
–
Air inlet
Drawing room
25
–
–
Air inlet
Rest room
25
18
–
Air inlet
Maintenance workshop with light physical work
45
–
–
Air inlet
Other workshops
60
–
–
Meeting
Independent
Meeting room
30
18
–
Catering
Air inlet
Dining room
30
22
–
Air inlet
Cafeteria
30
22
–
Child care facilities – Day care centers
Type of room
Flow rate (m3/h)
Labour code per person.
RSDT
per person.
per room
Air inlet
Secretariat – offices
25
–
–
Air inlet
Games and rest room
–
22
–
Teaching premises
Type of room
Flow rate (m3/h)
Labour code per person.
RSDT
per person.
per room
Teaching
Air inlet
Kindergarten, primary and junior high school classrooms
15
Air inlet
Senior high school and university classrooms
18
Air inlet
Home
18
Offices
Air inlet
Administration
25
18
Air inlet
CDI – library
25
18
Meeting
Air inlet
Multipurpose rooms
30
18
Catering
Air inlet
Dining room
30
22
Air inlet
Relay office
15 m3/h per meal
15 m3/h per meal
15 m3/h per meal
Premises for sports, para-sports and swimming pools
Type of room
Flow rate (m3/h)
Labour code per person.
RSDT
per person.
per room
Air inlet
Gymnasium – sports hall by sportsman
–
25
–
Air inlet
Gymnasium – sports hall per spectator
–
18
–
Air inlet
Pool
–
22
–
Air inlet
Lockers (N = number of lockers)
–
25
15 + 5N
Drinking / eating establishments
Type of room
Flow rate (m3/h)
Labour code per person.
RSDT
per person.
per room
Coffee
Air inlet
Bars, cafes
30
22
Air outlet
Kitchen
15 per meal
15 per meal
15 per meal
Air outlet
Reserves deposits
–
–
Catering
Air inlet
Lobby
30
22
Air inlet
Dining room
30
22
Air inlet
Cafeteria
30
22
Air outlet
Food reserve
0,4 / m2
Kitchen
Air outlet
Kitchen < 150 meals
25 per meal
25 per meal
25 per meal
Air outlet
Kitchen for 150 to 500 meals
20 per meal mini 3 750 m3 / h
20 per meal
20 per meal mini 3 750 m3 / h
Air outlet
Kitchen for 500 to 1,500 meals
15 per meal minimum 10 000 m3 / h
15 per meal mini 3 750 m3 / h
Air outlet
Cooking more than 1,500 meals
10 per meal min 22 500 m3 / h
15 per meal
10 per meal mini 3 750 m3 / h
Sanitary facilities
Type of room
Flow rate (m3/h)
Labour code per person.
RSDT
per person.
per room
WC
Air outlet
Isolated toilet
30
Air outlet
Grouped toilet (N = number of toilets)
30 + 15 N
Shower room
Air outlet
Grouped sinks (N = number of sinks)
10 + 5 N
Air outlet
Individual bathroom or shower
45
Air outlet
Individual bathroom or shower with WC
60
The flow rates indicated are the minimum fresh air flow rates to be taken into account for establishments receiving the public defined by the Labour Code for employees and the Standard Departmental Health Regulations for users (RSDT ). For the calculation of the flows, it will be taken into account the whole of the people frequenting these buildings.