Smart H

smarth

SMART H

Ventilate, heat, cool !

Smart H is a AHU (Air Handling Unit) providing thermodynamic energy recovery and adapted to your project in the tertiary sector.

 

BENEFITS

  • Thermodynamic double-flow AHU
  • Cooling or active cooling
  • Dehumidification
  • Tertiary adjusted ventilation with VOC detector and hygrometry
  • Automatic heating/cooling switch (change over)
  • Flat design (it can be assembled on a false ceiling)

Application

  • Decentralised AHU for tertiary environments up to 30 people
  • House (new or renovation)

Set-up

  • In an insulated plant room
  • Condensation to be predicted
  • Insulated air supply pipes (min. 25mm)
  • Insulated extraction pipes (min. 25mm)
  • Insulated pipes for release / fresh air 25mm or 50mm
  • Electricity: power supply 230V – 50Hz (2.5mm²)
  • Connection: 4 cables 0.5mm² max.

Air supply configurations available

configurations-smarth

Description

  • Automatic set-up
  • Compact single block without external units
  • White pre-lacquered aluminium finish 20/10
  • Heat and sound insulation
  • Heat pump on exhaust air, built-in
  • Rotary compressor, French
  • Low-consumption fans (EC ERF 2015)
  • Adjustable ventilation output
  • Device pre-loaded with R407C gas
  • Maintenance at the front
  • Wall stand with assembly instructions

Size

smart-plus-v-size1-en
smart-plus-v-size21

Range

DESIGNATION DESCRIPTION
MyDATEC Smart 200H unit KIT VMC thermodynamic double flow
Heating 3.9kW (of which 2kW for the upper heater)
Cooling 1.78kW (free cooling or active)
Wall stand
Touch control
KIT Centrale MyDATEC Smart 300H VMC thermodynamic double flow
Heating 5.1kW (of which 2kW for the upper heater)
Cooling 2.67kW (free cooling or active)
Wall stand
Touch control

Caractéristiques techniques

 

Smart 200H Smart 300H
COP (+7°C ext. / -7°C ext.) with 20°C inside

3,67 / 4,79

3.67 / 4.79

Heating power supplied at -7°C ext. / 20°C int.

1,9kW

3.1 kW

Heating pump standard
power absorption at +7°C ext. / 20°C int

0,52 kW

0.87 kW

EER at 35°C ext. / 27°C int.

2,41

2.39

Heating pump cooling power supplied
at 35°C ext. / 27°C int.

1,78 kW

2.67 kW

Nominal air flow to be considered
for thermal calculations

200 m3/h

300 m3/h

Maximum air flow configurable
(200 Pa)

600 m3/h

600 m3/h

Average intensity absorbed

2,3A

3,8A

Maximum power of
additional heaters

2 kW

Power supply

230 V – 50 Hz

Recommended protection

10 A courbe D

Filtering

G4

Refrigerant fluid

R 407 C

Mass of refrigerant fluid

900 g

Unit weight

60 Kg

smart-H-technica

smart-H-technical-2